Additional technical information: Dimensions W x L x H: (Incl. connection block and connection technology)50 mm x 107 mm x 50 mmFuse (short circuit): Internal electronic fuseNumber of inputs: 4Operating voltage range DC: 18 ... 30 VData format: 15 bits + signscales to 15 bitsDiagnostics: Wire break per channelLimit violation per channelParameter assignment errorOverflow/underflowOverload inputSensor supply short circuitInternal power consumption at operating voltage: Type. 50 mAOperating error limit in relation to ambient temperature range: +/- 0.3 %Basic error limit at 25 °C: +/- 0.2 %Internal cycle time: 500 µsCorrosion resistance class KBK: 1 - low corrosion stress(When installed)Storage temperature: -20 ... 70 °CLED displays: 1 group diagnostics4 Channel diagnosticsMax. Cable length 30 m.ShieldedNominal operating voltage DC 24 V.Rated operating voltage DC load voltage: 24V +/- 2%Parameterization: Data formatForce per channelLimit value monitoring/channelMeasurement smoothingSensor supply activeSignal range per channelShort circuit behaviorBehavior after overload inputMonitoring wire break/channelPotential separation channel - internal bus: Yes, without using the internal sensor supplyPotential separation channel - channel: No.Product weight: 46 gProtection type: Depending on the terminal blockSensor type: +/- 10V+/- 20mA+/- 5V(0 - 10 V)0 - 20 mA1-5 V4 -20 mAAmbient temperature: -5 ... 50 °CMaterial housing: PA-reinforcedPCMaterial note: RoHS compliantRepeatability 0.1% at 25 °C.; Ambient temperature (max.): +50 °C; Min. ambient temperature: -5 °C; Operating voltage: 24 V; Product size (height): 50 mm; Product size (length): 107 mm; Type: 573710; Weight: 46 g
Stockist | Price | |
---|---|---|
ConradElectronics01 | 605.03 | Visit Store |