Additional technical information: Dimensions W x L x H: (Incl. connection block and connection technology)50 mm x 107 mm x 50 mmFuse (short circuit): Internal electronic fuseNumber of inputs: 4Operating voltage range DC: 18 ... 30 VData format: 12 bits + signscales to 15 bitsDiagnostics: Wire break per channelLimit violation per channelInput signal short circuitParameter assignment errorInternal power consumption at operating voltage: Type. 50 mAOperating error limit in relation to ambient temperature range: +/- 0.6 %Basic error limit at 25 °C: +/- 0.5 %Internal cycle time: 10 msCorrosion resistance class KBK: 1 - low corrosion stress(When installed)Storage temperature: -20 ... 70 °CLED displays: 1 group diagnosticsMax. Cable length 30 m.ShieldedNominal operating voltage DC 24 V.Parameterization: Data formatForce per channelLimit value monitoring/channelMeasurement smoothingSignal range per channelShort circuit behaviorMonitoring wire break/channelPotential separation channel - internal bus: Yes, without using the internal sensor supplyPotential separation channel - channel: No.Protection type: Depending on the terminal blockSensor type 0 - 20 mA4 -20 mAAmbient temperature: -5 ... 50 °CMaterial housing: PA-reinforcedPCRepeatability 0.15% at 25 °C.; Ambient temperature (max.): +50 °C; Min. ambient temperature: -5 °C; Weight: 75 g
Stockist | Price | |
---|---|---|
ConradElectronics01 | 556.68 | Visit Store |
Additional technical information: Dimensions W x L x H: (Incl. linking block)50 mm x 107 mm x 55 mmNumber of inputs: 4Operating medium: Compressed air according to ISO 8573-1:2010 [7:4:4]Operating voltage range DC: 18 ... 30 VRepresentable unit(s): KPambarpsiData...
Additional technical information: Dimensions W x L x H: (Incl. connection block and connection technology)50 mm x 107 mm x 50 mmFuse (short circuit): Internal electronic fuseNumber of inputs: 4Operating voltage range DC: 18 ... 30 VData format: 15 bits...
Additional technical information: Dimensions W x L x H: (Incl. connection block and connection technology)50 mm x 107 mm x 50 mmFuse (short circuit): Internal electronic fuse per channelNumber of inputs: 4Operating voltage range DC: 18 ... 30 VData format:...